Description
The BDL99 device is designed to record and display current values as well as to present technological parameters in the form of graphs. The device is equipped with eight temperature Pt100/500/1000) or current (in the 0/4-20 mA standard) inputs, one pulse (digital) input for controlling the recording process and one USB Host port for flash data storage. The device has the memory capacity of 2 MB (0.5 million data recordings altogether) or 8 MB in version with USB (2 milions data recordings). However when a USB flash drive is plugged permanently, it can significantly extend the recording time without a need of data transfering from BDL99 to a PC. For example: 1GB flash drive allows continuous data recording for over 1 year (8 channels recorded every 1 sec., 250 millions data recordings)! The internal analogue-digital converter has a 16 bit resolution (12 bit in unit with 0/4-20mA inputs), which provides high recording resolution results. Additionally, individual alphanumeric description (text) of each of the recorded channels is possible. The menu assisted with full text descriptions makes the unit configuration process quite easy. However due to a significant number of configured parameters it is advised to use the attached configuration software for PCs.
Host port (front or rear) for flash data storage and configuration transfer. White or amber colour LCD backlight available.
Parameters
Inputs | 1, 4 or 8 x universal inputs: U/I (0/4-20 mA, 0/1-5 V, 0/2-10V or mixed) or temperature (Pt100/Pt500/Pt1000, TC K, S, J, T, N, R, B, E or mixed); 1 digital input 24V DC, optocoupled |
---|---|
Power supply | 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC |
Power consumption | typical 7 VA; max. 12 VA |
Outputs | 2 electronic relays (ER1, ER2) with max. load 24V AC (35V DC) / 200 mA; sensors supply (only current/voltage version): 24 V DC ± 5%, max. 200 mA, not separated from measuring inputs |
Case material | NORYL – GFN2S E1 |
Protection class | IP 65 (device front side, rear USB version), optional IP 65 version including gasket for panel cut-out sealing or IP 54 transparent door with key. IP 40 (front USB version) |
Operating temperature | 0°C ÷ +50°C (standard), -20°C ÷ +50°C (option) |
Display | graphic LCD, 128 x 64 points, with amber or white backlight |
Measurement range | mA (current) / V (voltage) inputs: ± 9999 + decimal point, resolution > 1mV; RTD inputs (Pt100, Pt500, Pt1000): -100.0°C ÷ +600.0°C with resolution 0,1°C; -148°F ÷ +999,9°F with resolution 0,1°F; TC inputs: -200°C ÷ +1370°C (K); -50°C ÷ +1768°C (S); -210°C ÷ +1200°C (J); -200°C ÷ +400°C (T); -200°C ÷ +1300°C (N); -50°C ÷ +1768°C (R); +250°C ÷ +1820°C (B); -200°C ÷ +1000°C (E); 0-60 mV, 0-75 mV, 0-100 mV or 0-150 mV |
Communication interface | RS-485 (Modbus RTU), galvanically isolated, transmission speed: 1200 – 115200 bit/sec., USB PC, USB Host port (front or rear) |
Data recording period | 1 s / 2 s / 5 s / 10 s / 15 s / 20 s / 30 s / 1 min / 2 min / 5 min / 10 min / 15 min / 20 min / 30 min / 60 min |
Internal memory capacity | 8 MB internal (up to 3 000 000 data records) |
Storage temperature | -10°C ÷ +70°C (standard), -20°C ÷ +70°C (depending on option) |
Case | panel mounting |
Case dimensions | 96 x 96 x 100 mm |
Panel cut-out dimensions | 90,5 x 90,5 mm |
Software | Free Loggy Soft and S-toolkit software for data recorder can be downloading directly from section „Download” |
Installation depth | min. 102 mm |