+46 (0)40 880 09 sales@basi.se
0 Items

Digital Indicator BDI73

The BASI programmable process indicator BDI73 is designed for wide range of control applications.

Description

The BASI programmable process indicator BDI73 meter in small case, with current-voltage or mV input, with 1 or 2 relay (or OC type) outputs. The version without relay outputs is also available.

Parameters

Inputs current 0-20 mA or 4-20 mA, programmable, input resistance < 65 Ohm (typ. 55 Ohm), overload-protected, input current limited to 40 mA; voltage 0-5 V, 1-5V, 0-10V or 2-10V, programmable, input resistance > 50 kOhm; milivoltage 0-60 mV, 0-75 mV, 0-100 mV, 0-150 mV; programmable; input resistance > 100 kOhm
Power consumption for 85 ÷ 260V AC/DC and 16V ÷ 35V AC power supply: max. 4,5 VA; 19V ÷ 50V DC power supply: max. 4,5 W
Outputs 0, 1 or 2 relays 1A/250V AC (cos fi=1) or the OC 30mA/30VDC/100mW; transducer power supply output: 24V DC +5%, -10% / max. 100 mA, stabilized, not insulated from measuring inputs
Case material NORYL- GFN2S E1
Protection class depending on display size: for 5 x 9 mm display: IP 65 (front), available additional frame IP 65 for panel cut-out sealing; IP 20 (case and connection clips); for 4 x 13 mm display: IP 40 (front); IP 20 (case and connection clips)
Display LED, two-coloured (red-green), 4 x 13 mm (IP 40) – standard or LED, red, 5 x 9 mm (IP 65) – option
Operating temperature 0°C ÷ +50°C (standard), -20°C ÷ +50°C (option)
Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Measurement range -999 ÷ 9999 + decimal point
Accuracy ± 0,25% ± one digit in the entire operation range
Communication interface RS-485, 8N1 and 8N2, 1200 bit/s ÷ 115200 bit/s, Modbus RTU (not galvanically isolated from measuring inputs)
Stability typ. 50 ppm/°C
Storage temperature -10°C ÷ +70°C, -20°C ÷ +70°C (with option 08)
Case dimensions 72 x 36 x 97 mm
Case panel mounting
Panel cut-out dimensions 66,5 x 32,5 mm
Installation depth min 102 mm