Digital Flow Indicator BFCI94

BFCI-94 are the flow meters designed to work in tandem with the pulse flow transducers with coefficients ranging from 0,01 to 9999,99 pulses per litre, equipped with electronic (open collector) or contact input. A flow counter allows to measure the actual instantaneous value and to record the total flow of fluids, gases or bulk materials. Wide range of total flow (up to 16 significant digits) enables flow volume control for a long time.

Description

BFCI-94 are the flow meters designed to work in tandem with the pulse flow transducers with coefficients ranging from 0,01 to 9999,99 pulses per litre, equipped with electronic (open collector) or contact input. A flow counter allows to measure the actual instantaneous value and to record the total flow of fluids, gases or bulk materials. Wide range of total flow (up to 16 significant digits) enables flow volume control for a long time. Build in a batcher function makes possible application of BFCI-94 in a wide range of industry branches (food production, pharmacy, paint and varnish). The REL / OC control outputs can adjust the level of measured signal and are controlled according to one or two threshold values. Moreover, the meter can be equipped with analogue outputs, according to the customer selection: active current output, passive isolated current output or active voltage output. The meter can be configured with the local keyboard or free S-Config software via the RS-485 communication port.

Parameters

Inputs pulse galvanically isolated with contacts oscillation damping, max. frequency from 10 kHz; reset of totalizer counter: edge or level triggered, galvanically isolated
Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Power consumption for 85 ÷ 260V AC/DC and 16V ÷ 35V AC power supply: max. 4,5 VA; 19V ÷ 50V DC power supply: max. 4,5 W
Protection class IP 65 (front), available additional frame IP 65 for panel cut-out sealing; IP 20 (case and connection clips)
Display LED, red, 6 x 13 mm high
Operating temperature 0°C ÷ +50°C (standard), -20°C ÷ +50°C (option)
Measurement range 0 ÷ 999999 + decimal point
Accuracy instantaneous flow values: selected in the range 0 ÷ 0,00000; balance accuracy: selected in the range from ± 1 to ± 0,0001
Analogue outputs (available with 2 x REL or OC, see ordering): active current: operating range 0/4-20 mA (max. 0-24 mA), load resistance 700 Ω max., resolution 13 bit passive current: isolated, operating range 4-20 mA (max. 2,8-24 mA), load resistance 600 Ω@24VDC, resolution 13 bit; active voltage: operating range 0/1-5V, 0/2-10V (max. 0-11V), load resistance min. 2000 Ω, resolution 13 bit
Instantaneous flow unit l or m3 per second, minute or hour
Total flow unit I or m3
Pulse waiting time settable from 0,1 do 39,9 seconds
Total flow capacity over 4 x 10^9 pulses (max. 16 significant digits)
Data memory non-volatile memory, EEPROM type
Communication interface RS-485 / Modbus RTU (not galvanically isolated)
Output 2 or 4 relay 1A/250V AC (cos fi=1) or OC 30mA/30VDC/100mW; power supply output: 24V DC + 5% -10% / max 100 m
Transmission parameters 1200 ÷ 115200 bit/s, 8N1 and 8N2
Storage temperature -10°C ÷ +70°C or -20°C ÷ +70°C (depending on version)
Case panel mounting
Case dimensions 96 x 48 x 100 mm
Panel cut-out dimensions 90,5 x 43 mm
Instantaneous flow precision selected from range: 0 ÷ 0.00000
Total flow precision selected from range: 0 ÷ 0.000
Installation depth min 102 mm