Digital Indicator BDI94U

Meter with large, readable display, with universal input (0/4-20mA, 0-10V, 0-150 mV, Pt 100/500/1000 or TC type K, S, J, T, N, R, B, E), with 0, 2 or 4 relay (or OC type) outputs and 1 analogue output, according to the customer selection: active current output, passive isolated current output or active voltage output. The meter can be configured with the local keyboard or free S-Config software via the RS-485 communication port.

Description

BDI94U meter/transmitter is equipped with one universal input, type: 0/4-20mA, 0-10V, 0-150 mV, Pt 100/500/1000 or TC (K, S, J,T, N, R, B, E). During the measurement process only one kind of inputi s available.Temperature of cold ends is compensated automatically. RTD and TC inputs are fully linearised. The device with current or voltage input operates in the following modes: linear, root, square and user de_ned (max. 20 points). Result is shown on 4-digit LED display. The device is equipped with RS-485/Modbus RTU communication interface and sensor supply output. 2 or 4 relay (or OC) outputs make it possible to adjust the level of the measured signal. These outputs can be controlled according to one or two threshold values. OptionallyBDI94Uwith two relays outputs can be equipped witha ative currento utput. Thed evice can be usedfor controlling and regulation of processes need proportional and thresholdc ontroll ike: temperature processes (heating or cooling), valves controlling or other.

Parameters

Inputs universal (programmable): current; voltage; milivoltage; thermoresistance or thermocouple type K, S, J, T, N, R, B, E
Power consumption for 85 ÷ 260V AC/DC and 16V ÷ 35V AC power supply: max. 4,5 VA; 19V ÷ 50V DC power supply: max. 4,5 W
Outputs 0, 2 or 4 relays 1A/250V AC (cos fi=1) or the OC 30mA/30VDC/100mW; transducer power supply output: 24V DC +5%, -10% / max. 100 mA, stabilized, not insulated from measuring inputs
Case material NORYL- GFN2S E1
Measurement range current: 0-20 mA or 4-20 mA, voltage 0-5 V, 1-5V, 0-10V or 2-10V, milivoltage 0-60 mV, 0-75 mV, 0-100 mV or 0-150 mV; thermoresistance: Pt100, Pt500, Pt1000, measuring range -100°C ÷ 600°C; thermocouple K: -200°C ÷ +1370°C; S: -50°C ÷ +1768°C; J: -210°C ÷ +1200°C; T: -200°C ÷ +400°C; N: -200°C ÷ +1300°C; R: -50°C ÷ +1768°C; B: +250°C ÷ +1820°C; E: -200°C ÷ +1000°C
Protection class IP 65 (front), available additional frame IP 65 for panel cut-out sealing; IP 20 (case and connection clips)
Operating temperature 0°C ÷ +50°C (standard); -20°C ÷ +50°C (option)
Display LED, red (green on request), 4 x 20 mm high
Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Accuracy 0.1% @25°C (inputs: current, voltage, milivoltage, thermoresistance, thermo-couple K, J, E); 0.2% @ 25°C (thermocouple N), 0.5% @25°C (thermocouple S, T, R, B)
Analogue outputs (available with 2 x REL or OC, see ordering): active current: operating range 0/4-20 mA (max. 0-24 mA), load resistance 700 Ω max., resolution 13 bit passive current: isolated, operating range 4-20 mA (max. 2,8-24 mA), load resistance 600 Ω@24VDC, resolution 13 bit; active voltage: operating range 0/1-5V, 0/2-10V (max. 0-11V), load resistance min. 2000 Ω, resolution 13 bit
Stability 50 ppm/°C
Communication interface RS-485, 8N1 and 8N2, 1200 bit/s ÷ 115200 bit/s, Modbus RTU (not galvanically isolated from measuring inputs)
Displayed values range -999 ÷ 9999 + decimal point
Storage temperature -10°C ÷ +70°C; -20°C do +70°C (depending on version)
Case dimensions 96 x 48 x 100 mm
Case panel mounting
Panel cut-out dimensions 90,5 x 43 mm
Installation depth min. 102 mm

Title Type Size
Data Sheet application/pdf 224 KB